4X/7-350235JB Control Thermostats
The 4X/7-350235JB, equipped with a double-pole switch, is designed for use as an adjustable control thermostat for freeze protection and temperature maintenance applications requiring pipewall or tankwall sensing. The design of the thermostat permits its use as a junction box for connecting the heating cable to power by using the optional mounting kit (TM4X for ordinary locations or TM7 for Division 2 hazardous locations). The thermostat features an epoxy- coated cast aluminum NEMA 4X/NEMA 7 enclosure to provide watertight, dust tight, corrosion-resistant and explosion proof protection to the thermostat switch
FEATURES
- Epoxy- coated cast aluminum NEMA 4X/NEMA 7 enclosure
- Adjustable control thermostats for freeze protection and temperature maintenance applications
- Certified for use in ordinary (nonclassified) areas and hazardous (classified) locations
APPLICATION
The 4X/7-350235JB, equipped with a double-pole switch,
is designed for use as an adjustable control thermostat
for freeze protection and temperature maintenance
applications requiring pipewall or tankwall sensing. The
design of the thermostat permits its use as a junction
box for connecting the heating cable to power by using
the optional mounting kit (TM4X for ordinary locations or
TM7 for Division 2 hazardous locations). The thermostat
features an epoxy- coated cast aluminum NEMA 4X/NEMA
7 enclosure to provide watertight, dust tight, corrosionresistant and explosion proof protection to the thermostat
switch.
The 4X/7-350235JB thermostat is approved for use in
both ordinary (nonclassified) and hazardous (classified)
locations.
RATINGS
Voltage rating…………………………………..125/240/277 Vac
Switch rating………………………………………………. 25 amps
Switch type ……………………………………………………. DPST
Electrical connection 1 …………screw terminals on switch
Adjustable control range…. 35°F to 235°F (2°C to 113°C)
Maximum control differential ……………………….9°F (5°C)
Maximum bulb exposure temperature…….300°F (149°C)
Bulb dimensions ……………… 1/4” x 6-3/8” (6.4 x 162 mm)
Bulb material……………………………….nickel-plated copper
Capillary length…………………………………………..6’ (1.8 m)
Capillary material…………………………nickel-plated copper
Capillary armor ………………………… flexible stainless steel
Notes
1. The 4X/7-350235JB utilizes two 1” NPT conduit hub openings for the mounting
expediter and incoming power. The thermostat includes an internal grounding
terminal.